In this post, we will embark on an in-depth exploration of the intricate specifications pertaining to HT and LT Stays. The realm of stay specifications represents a fundamental aspect of electrical engineering, warranting meticulous attention and consideration. As we delve into this subject matter, we shall navigate the intricacies and nuances of HT and LT Stays, shedding light on their precise specifications and how they contribute to the robustness and reliability of electrical systems.
Related Keyword :
LT STAY Set Specification
LT Stay Sets are a set of hardware components meticulously designed to support and stabilize low tension electrical lines. These lines typically carry voltages below 1,000 volts and are commonly found in residential and commercial areas. While they may not carry the high voltages of their high-tension counterparts, LT lines are integral to our daily lives, powering homes, offices, and a myriad of devices.LT Stay Specification, 16mm Stay Specification
Below list gives all the details of LT Stay
Part's/Section Name | Size in MM |
---|---|
Stay Rod Length | 1680 |
Thread Length | 300 |
Diameter of Stay Rod | 16 |
C.I Bow Height | 400 |
Hole to Hole | 84 |
Casting Length | 128 |
Casting Thickness | 12 |
Casting Height | 45 |
Diameter of Bow Rod | 12 |
Plate | 150 Sq. |
Size of Hole | 18 Sq. |
Plate Thickness | 6 |
Thimble Length | 65 |
Thimble Width | 45 |
Groove Portion | 16 |
Thickness | 2.64 |
1 set LT Stay Weight | 5.6 Kg |
HT STAY Set Specification
HT Stay Sets, short for High Tension Stay Sets, are an essential component of electrical transmission and distribution systems. They are meticulously engineered assemblies designed to provide structural support and stability to utility poles, towers, and other structures that carry high voltage electrical conductors.
HT Stay Specification, 20mm Stay Specification
Below list gives all the details of HT Stay
Part's/Section Name | Size in MM |
---|---|
Stay Rod Length | 1830 |
Thread Length | 300 |
Diameter of Stay Rod | 20 |
C.I Bow Height | 400 |
Hole to Hole | 115 |
Casting Length | 150 |
Casting Thickness | 14 |
Casting Height | 55 |
Diameter of Bow Rod | 16 |
Plate | 230 Sq. |
Size of Hole | 22 Sq. |
Plate Thickness | 6 |
Thimble Length | 70 |
Thimble Width | 47 |
Groove Portion | 20 |
Thickness | 2.8 |
1 set HT Stay Weight | 10 Kg |
LT & HT Stay Related MCQs
Q: Length of LT Stay Rod?
A: 1680 MM, Dia-16 MM
Q: LT Stay Plate Size?
A: 150 X 150 X 6 MM
Q: LT Stay Plate Hole Size?
A: 18mm SQ.
Q: Dia of LT Stay Rod?
A: 16 MM
Q: Pole Top to Guy Insulator Distance?
A: 1.5 Mtr.
Q: Size of LT Stay Wire?
A: 7/12 SWG or 7/10 SWG (It depends on approval)
Q: 7/12 SWG Stay wire weight per meter?
A: 0.308 Kg/m (Approx.)
Q: LT Guy Insulator Length?
A: 90x65 MM
Q: LT Guy Insulator Specification?
A: Size- 90x65 mm, Failing Load- 44 KN, Weight- 500 gms. Approx.
Q: Length of HT Stay Rod?
A: 1830 MM
Q: Dia of HT Stay Rod?
A: 20 MM
Q: HT Stay Plate Size?
A: 230 X 230 X 6 MM
Q: HT Stay Plate Hole Size?
A: 22mm SQ.
Q: HT Guy Insulator Length?
A: 140 X 85 MM
Q: HT Guy Insulator Specification?
A: Size- 140x85 mm, Failing Load- 53 KN, Weight- 750 gms. Approx
Q: Stay Wire Binding Length?
A: 225 MM
Q: 7/10 SWG Stay wire weight per meter?
A: 0.448 Kg/m (Approx.)
Q: 7/14 SWG Stay wire weight per meter?
A: 0.180 Kg/m (Approx.)
Q: How many Kg of Stay Wire is Required for a Single Stay?
A: 7/10 SWG- 4.9 Kg, 7/12 SWG- 3.38 Kg.
Q: Pole to Stay Distance?
A: 6 Mtr. (20 ft)
Related Keyword :
HT Stay Specification
LT Stay Specification
20mm Stay Specification
16mm Stay Specification
1680X16mm Stay
1830X20mm Stay
Stay Specification